From (3), (13) and (14), it is shown that when Th -Tc>△Tmax, the cooling capacity qc<0. At the same time, TEC cannot cool, but start heating, which is not allowed in practical work. So the working current should be controlled in range of I0≤I≤Isat, which can ensure the cooling capacity qc≥0. Although based on the analysis of the cooling capacity qc, the general range of working current can be determined, but in practical work, the refrigeration coefficient is still an important indicator. From (9), when the working current of TEC satisfies the following relations, the TEC can reach the maximum refrigeration coefficient βmax: